| Info: | |
| Data type: |
Description:
With Automation Studio versions before V3.0, the node numbers of all ACOPOS modules that are configured in the hardware tree, are entered into the module acp10cfg. This error is displayed, if for a POWERLINK interface a node number is defined more than once.
Note:
If this error occurs, the following error with this error number in the binary data is entered in the Logger:
- 10550: Read NC CFG module: NC manager error in 'Binary Data'
In addition, the following error with the status value "if_index*256 + node_nr" in the binary data is entered in the Logger:
- 10551: Read NC CFG module: Status for NC manager error in 'Binary Data'
Reaction:
Initialization of the NC software is aborted. No NC object can be operated.
Cause/Remedy:
Define each node number for ACOPOS modules at each POWERLINK interface only once.
Rebuild module acp10cfg and transfer it to the target.
Change of the NC software version.
Change of the Automation Studio version.