32079: With this variant one CAN interface must be in module acp10cfg

Info:
Data type:

Description:
When using this ACP10MAN variant (ACP10MAN for CAN), a CAN interface must be contained in the module acp10cfg. If this is not the case, this error is displayed.

Note:
If this error occurs, the following error with this error number in the binary data is entered in the Logger:
- 10550: Read NC CFG module: NC manager error in 'Binary Data'

Reaction:
Initialization of the NC software is aborted. No NC object can be operated.

Cause/Remedy:
Insert a CAN interface in the ACP10 configuration.
Rebuild module acp10cfg and transfer it to the target.
Insert another ACP10MAN Variant (ACP10MAN for POWERLINK) into the project and transfer it to the target.