| Info: | |
| Data type: |
Description:
When using this ACP10MAN variant (ACP10MAN for POWERLINK), a POWERLINK interface must be contained in the module acp10cfg. If this is not the case, this error is displayed.
Note:
If this error occurs, the following error with this error number in the binary data is entered in the Logger:
- 10550: Read NC CFG module: NC manager error in 'Binary Data'
Reaction:
Initialization of the NC software is aborted. No NC object can be operated.
Cause/Remedy:
Insert a POWERLINK interface in the ACP10 configuration.
Rebuild module acp10cfg and transfer it to the target.
Insert another ACP10MAN Variant (ACP10MAN for CAN) into the project and transfer it to the target.