32087: With this variant no POWERLINK interface is allowed in module acp10cfg

Info:
Data type:

Description:
If a POWERLINK interface is contained in the module acp10cfg when using this ACP10MAN variant (ACP10MAN for POWERLINK), this error is displayed.

Note:
If this error occurs, the following error with this error number in the binary data is entered in the Logger:
- 10550: Read NC CFG module: NC manager error in 'Binary Data'

Reaction:
Initialization of the NC software is aborted. No NC object can be operated.

Cause/Remedy:
Delete the POWERLINK interface in the ACP10 configuration.
Rebuild module acp10cfg and transfer it to the target.
Insert another ACP10MAN Variant (ACP10MAN for POWERLINK) into the project and transfer it to the target.