35072: SMC FS: Homing - SMP window is greater than safe absolute encoder range

Info:
Data type:

Description:
Configuration error of encoder homing. The SMP is configured and the SMP position window is greater than the safe absolute encoder counting range.

Reaction:
The module changes into Fail Safe state.

Cause/Remedy:
Check the absolute encoder counting range of the connected encoder!
Check the parameter "SMP - Lower position limit"!
Check the parameter "SMP - Upper position limit"!
Carry out a Power Down/Power Up cycle!