35125: SMC FS: RSP - Save operation failed

Info: Additional info
Data type: UDINT

Description:
Internal error, during the save operation of remanent safe position.

The additional information (Info1) provides the reason for the error.
0x0001 ... Timeout or received data frame.
0x0002 ... Data frame check missmatch.
0x0003 ... Release of receive buffer failed.
0x0004 ... Sending of send buffer failed.
0x0005 ... Data frame with wrong framelength received.
0x0006 ... Send buffer can't be request

Offset information for safety logger:
binary data[20..17]: Info1

Reaction:
The module changes into Fail Safe state.

Cause/Remedy:
If this error is everlasting call technical support!