| Info: | Additional info |
| Data type: | UDINT |
Description:
Internal error, during the save operation of remanent safe position.
The additional information (Info1) provides the reason for the error.
0x0001 ... Timeout or received data frame.
0x0002 ... Data frame check missmatch.
0x0003 ... Release of receive buffer failed.
0x0004 ... Sending of send buffer failed.
0x0005 ... Data frame with wrong framelength received.
0x0006 ... Send buffer can't be request
Offset information for safety logger:
binary data[20..17]: Info1
Reaction:
The module changes into Fail Safe state.
Cause/Remedy:
If this error is everlasting call technical support!