| Info: | Additional info |
| Data type: | UDINT |
Description:
Configuration error in function SafeUserData!
The additional information (Info1) shows the details:
0x00000001 ... "Safe User Data 1 (4 Byte) - Channel" configured, but ControlSwitchUserData is not connected.
0x00000002 ... "Safe User Data 1 (4 Byte) - Channel" set to "Disabled", but ControlSwitchUserData is connected.
Offset information for safety logger:
binary data[20..17]: Info1
Reaction:
The module changes into Fail Safe state.
Cause/Remedy:
Check Safe User Data.
Check the parameters in the safety application.