35154: SMC FS: Additional safety parameters: Invalid structure size

Info: Additional info
Data type: UDINT

Description:
The specified size of the safe machine options in the functional
application does not match the expected size of the set structure version.
The additional information (Info1) shows the details:
Info1: 0xaaaabbbb
aaaa ... Specified size of the safe machine options in the data structure (StructInfoSize)
bbbb ... Maximum accepted size of the safe machine options structure

Offset information for safety logger:
binary data[20..17]: Info1

Reaction:
The module changes into Fail Safe state.

Cause/Remedy:
Check the functional application!