| Info: | Additional info |
| Data type: | UDINT |
Description:
While processing the safe machine options an error occurred.
The additional information (Info1) shows the details:
0x00000000 ... The specified size of the safe machine options structure is invalid.
0xssss0001 ... The expected data is the OpenSAFETY header but the size of the received data does not
match the size of the OpenSAFETY header. "ssss" contains the actual size of the received data
0x00000002 ... Error while calculating the CRC32 of the received safe machine options.
0x00000003 ... Invalid request code when receiving data from the SCM.
0x00000004 ... Invalid request code when requesting data from the SCM.
0xaaaa0005 ... Invalid state of the download process when changing to "Operational" state.
"aaaa" is the number of the state which caused the error
0xiiii0006 ... Error while parsing the received data for the safe machine options.
"iiii" is the index of the parameter which causes the error
0x00000007 ... Error while re-setting the module into "Pre-Operational" state.
0xiiii0008 ... Received safe machine options with invalid parameter index.
"iiii" is the parameter index of the received parameters
0xvvvv0009 ... Received safe machine options with invalid OpenSAFETY header version.
"vvvv" contains the version of the received openSAFETY header.
0xssss000A ... Invalid state during initialization. "ssss" represents the index of the state.
0x0000000B ... Invalid bit offset passed to the map-function
Offset information for safety logger:
binary data[20..17]: Info1
Reaction:
The module changes into Fail Safe state.
Cause/Remedy:
Check the functional application if the correct structure version is used!