| Info: | Square of the actual stator current vector |
| Data type: | UDINT |
Description:
At the beginning of the Safe Brake Test actual load of the axis is latched, if the parameter "SBT - External load" is configured (unequal to zero).
This value is outside the tolerance of "SBT - External load" +/-6,25%.
The measured value is not equal to the configured external load.
The additional data (Info1) shows the squared measured value.
Offset information for safety logger:
binary data[20..17]: Info1
Reaction:
A warning is created.
The Safe Brake Test status is cleared.
Cause/Remedy:
The external (e.g. hanging) load has changed.
Check the parameter "SBT - External load"!
Check the functional brake test sequence!