35215: SMC FFS: Alive test - Monitoring timeout

Info:
Data type:

Description:
Error during an activated Alive-Test. The plausibility check (alive test) of the set position has not been done within 15min after power on!

Reaction:
The module changes into Functional Fail Safe state.

Cause/Remedy:
Check the application!
A 24-hour timeout begins after successfully checking the plausibility of the setpoint.
The SPA bit is set and timeout is reset any time the position setpoint changes by more than twice the position lag error
tolerance.
Note the configuration rule for position lag error tolerance from the user's manual.