39315: Analog IO: Analog input: Analog value above the measuring range

Info: Analog IOs
Data type: USINT

Description:
Runtime error on analog input.
The analog value is above the measuring range.

Reaction:
The analog value is limited to the maximum value.

Cause/Remedy:
Wire break on the analog input plus.
The applied voltage is above the measuring range.
Connection is interrupted or defective. See wiring guidelines error number 7030.
Plug-in card defective.