7049: Abnormal encoder current consumption

Info: Encoder
Data type: USINT

Description:
Encoder power consumption has dropped below a specified level.

Reaction:
See error number 7030.

Cause/Remedy:
If the encoder is powered externally, this monitoring must be switched off. See parameter PARID_ENCOD_LINE_CHK_IGNORE.
No encoder supply or supply contains an error.
+5V, +24V or COM not connected.
See wiring guidelines error number 7030.
Encoder/Module defective.
Encoder power consumption < 150mW (5V)
Encoder power consumption < 200mW (24V)