Description:
Runtime error. At least one mains phase failed.
The following modules do not have phase failure monitoring:
|------------------------------------------------------| | 8V1022.00-1 | | 8V1045.00-1 | | 8V1090.00-1 | | 8V1022.00-2 from Rev.:A0 up to and including Rev.:F0 | | 8V1045.00-2 from Rev.:A0 up to and including Rev.:F0 | | 8V1090.00-2 from Rev.:A0 up to and including Rev.:F0 | | 8BVP | | 8C | | 8D | | 8E | | 80 | |------------------------------------------------------|
Reaction:
ACOPOS: See error number 7211.
ACOPOSmulti: None.
Cause/Remedy:
See Power unit
Mains wiring error: Loose contact or mains phase not attached. -> Check wiring and voltages on the mains connection.
Mains phase failure: Check the contactor, fuse, transformer and supply voltage.
DC bus feed or single-phase operation: If the ACOPOS module is supplied by the DC bus or single-phase, then the phase monitor must be ignored (PHASE_MON_IGNORE = 1). Caution: These operating modes are only conditionally permissible.