7215: Power mains: At least one phase of the power line failed

Info:
Data type:

Description:
Runtime error. At least one mains phase failed.

The following modules do not have phase failure monitoring:

|------------------------------------------------------|
| 8V1022.00-1                                          |
| 8V1045.00-1                                          |
| 8V1090.00-1                                          |
| 8V1022.00-2 from Rev.:A0 up to and including Rev.:F0 |
| 8V1045.00-2 from Rev.:A0 up to and including Rev.:F0 |
| 8V1090.00-2 from Rev.:A0 up to and including Rev.:F0 |
| 8BVP                                                 |
| 8C                                                   |
| 8D                                                   |
| 8E                                                   |
| 80                                                   |
|------------------------------------------------------|


Reaction:
ACOPOS: See error number 7211.
ACOPOSmulti: None.

Cause/Remedy:
See Power unit

Mains wiring error: Loose contact or mains phase not attached. -> Check wiring and voltages on the mains connection.

Mains phase failure: Check the contactor, fuse, transformer and supply voltage.

DC bus feed or single-phase operation: If the ACOPOS module is supplied by the DC bus or single-phase, then the phase monitor must be ignored (PHASE_MON_IGNORE = 1). Caution: These operating modes are only conditionally permissible.