| Info: | Maximum DC bus voltage |
| Data type: | REAL |
Description:
Runtime error using the 'switch on controller' command.
The main relay is open.
When the controller is turned on, the filtered DC bus voltage UDC_FILTER is checked.
The error is generated, if the filtered DC bus voltage UDC_FILTER is higher than the threshold voltage of the braking resistor UDC_BLEEDER_ON or higher than the following module-dependent limit voltage.
|--------------------|----------------------------------| | 8Vxxxx.00-x | 746 VDC (1.1*sqrt(2)*480VAC) | | 8Vxxxx.50-x | 357 VDC (1.1*sqrt(2)*230VAC) | | 8BxP | 746 VDC (1.1*sqrt(2)*480VAC) | | 8C | 880 VDC | | 8D | 880 VDC | | 8EIxxxHxxxx.xxxx-x | 825 VDC | | 8EIxxxMxxxx.xxxx-x | 358 VDC | | 80 | 88 VDC | |--------------------|----------------------------------|
Reaction:
See error number 7210.
Cause/Remedy:
See Power unit
Invalid mains: Supply voltage or DC bus voltage is too high. -> Check the DC bus voltage.