| Info: | Limit |
| Data type: | REAL |
Description:
Runtime error if the absolute value of the summation current (= |VCTRL_I0| = |VCTRL_I1 + VCTRL_I2 + VCTRL_I3|) exceeds the module-dependent limit VCTRL_I0_LIM (see info):
Reaction:
See error number 7224.
Cause/Remedy:
Ground is connected to the inverter output on contact U, V or W
Capacitive load: When using long motor cable (> 50m) or cable form third-party manufacturer.
Unstable current controller: See error number 9300.
-> In situations with high currents and high current change rates, dynamic current transformer errors can cause the measured summation current value to be too high.