| Info: | Detected frequency |
| Data type: | REAL |
Description:
Runtime error when switching on the controller if the absolute value of the detected mains frequency (see INFO) is outside the range [20,200]Hz.
Reaction:
The inverter power stage is switched off.
Cause/Remedy:
Check the mains frequency.