9010: Temperature sensor (Motor|Choke|External): Stop limit exceeded

Info: Temperature limit
Data type: REAL

Description:
Runtime error if the temperature of the motor temperature sensor TEMP_MOTOR exceeds the limit (see INFO).

Reaction:
See error number 9000.

Cause/Remedy:
Invalid operational conditions:
- Environmental temperature too high. -> Check the motor specifications.
- Flange temperature too high. -> Check the motor specifications.
- Cooling is defective. -> Check any necessary air or water cooling.

Motor continuous current exceeded:
- Increased current. See error number 9030. -> Determine the medium speed and the effective value of the motor current and compare these values with the continuous current curve (S1 operation) of the motor.

Problem with motor temperature measurement:
- Sensor defect: -> When the controller is switched off, compare the environmental temperature with TEMP_MOTOR.
- Sensor not connectable: The error is reported on the second axis of the single axis module.
- Disturbance: Motor temperature sensor on connector cable missing or poorly shielded. Check motor temperature TEMP_MOTOR for disturbance pulses.
- Defective isolation of the temperature sensor
- ACOPOS module defect

The maximum motor temperature (=110°C) is too low.