9070: Motor temperature model: Stop limit exceeded

Info: Temperature limit
Data type: REAL

Description:
Runtime error if the condition TEMP_MOTOR_MODELL > TEMP_MOTOR_MODEL_LIM is fulfilled.
See Motor temp model

Reaction:
See error number 9000.

Cause/Remedy:
Current increased: See error number 9030.

Incorrect motor configuration:
-> Compare the motor rated current MOTOR_CURR_RATED with the motor specifications.
-> Compare the motor stall current MOTOR_CURR_STALL with the motor specifications.
-> Check the den motor winding cross section MOTOR_WIND_CROSS_SECT.