38009: Inverter: Output: Current flow test aborted

Info: Phase
Data type: USINT

Description:
Runtime warning when switching on the current controller. When the controller is switched on, it is checked whether current can be injected into the phases of the motor or regenerative choke (inverter output) by voltage setting. Before testing, the range of the current measurement signal is greater than sqrt (2) * MIN (MOTOR_CURR_RATED, ACOPOS_CURR_RATED). This means that the current flow test cannot be performed.

Reaction:
None

Cause/Remedy:
See error number 6045.

The motor wiring is not correct. Check the motor wiring and shielding.
The motor is not matched to the inverter. Rated motor current MOTOR_CURR_RATED is much lower than rated inverter current ACOPOS_CURR_RATED.