6030: Holding brake: Brake output is active, but no brake entered in motor data

Info:
Data type:

Description:
Runtime error using the 'switch on controller' command when holding brake monitor is active. Current is flowing to the holding brake output even though a holding brake was not specified in the motor configuration data.

Reaction:
See error number 6045.

Cause/Remedy:
Incorrect motor configuration data for the holding brake.
The output for the holding brake is being used for another functionality and the brake monitor has not been deactivated (bit 2 in the BRAKE_MODE not set).