B&R IMC400 Monitor Service Guide


1. Purpose

To clearly guide service engineers on differences in program configurations by CPU type when using IMC400-based monitors, and to outline precautions when replacing or modifying CPUs.


2. IMC400 Monitor Configuration and Classification

Monitor ModelSizeApplied CPU상태Main Applied Models
PP48012″IMC400_4PPDiscontinuedTE only
PP58015″IMC400_5PPDiscontinuedDL, VH, TH, TE
PP210015″IMC400_PP2100In UseDL, VH, THA5, TEA5

3. Program Configuration by CPU

  • IMC400 program structure differs depending on CPU board configuration.
  • When a CPU is discontinued or replaced, the same program cannot be applied directly.
  • The following three items are mandatory when requesting program modification:
    1. CPU card configuration (e.g., 4PP, 5PP, 2100)
    2. Program version and configuration details
    3. Machine model and applied options

→ If any of the above information is missing, program rebuild and download are not possible.


4. Dynamic Configuration Feature (PP2100 Only)

  • PP2100 used in TH, VH, and TE models adopts a Dynamic Configuration structure.
  • Optional cards (e.g., I/O, communication, temperature cards) can be selectively enabled via the monitor application.
  • Service engineers must verify option settings before downloading or replacing programs.
  • Due to Dynamic Configuration, separate programs for different machine configurations are not required.

5. Exception for DL Models

  • IMC400 for DL models maintains a static configuration approach.
  • Dynamic Configuration is not applied.
  • When replacing programs, the existing CPU and hardware configuration must be kept identical.

6. Service Key Message Summary

ItemKey Content
Required for Program RequestCPU configuration, program configuration, machine model/options
IMC400 CPU ReplacementDirect copy not possible due to different program structure
PP2100 ModelDynamic Configuration applied, options reflected via settings
DL ModelsStatic configuration maintained
CautionR&D approval required before any program modification


 
PP480
 
PP580
 
PP2100

TAG: IMC400, B&R, service guide, dynamic configuration, CPU configuration, monitor system, PLC, control engineering